Maintaining commercial HVAC economizers –
Part 1
Introduction
Economizers bring in outside
air for ventilation and for free cooling.
However outside air may be too warm or too humid to offer free cooling
or very cold. Additional outside air
that must be conditioned increases the cooling and/or heating load on the building. Economizers that are properly designed,
maintained and set can save significant amounts of energy. However economizers
that are not functional, leaking, have sensors out of calibration or miss-set
can have large energy penalties.
Maintaining economizers is critical to their function and to their
impact on energy use.
This document sets out some
basic information about commercial HVAC air-side economizers as well as an
expanded maintenance checklist. See: Maintaining
commercial HVAC economizers – Part 2 for specific step-by-step economizer
performance testing designed to be compatible with price sensitive commercial
maintenance contracts. Please Press "Read More"
Background/Notes
1. There
are two basic types of economizers
a.
Analog
b.
Digital
2. There
are two basic types of change-over sensors
a.
Dry-bulb
i.
Analog
1. C7650
– 10°F operational dead band
2.
C7660 – 2°F dead band
+/- 1°F hysteresis
ii.
Digital
b.
Enthalpy
i.
Analog
1. Were
accurate at 40%-70% RH +/- 5%, +/-10%
outside that range
2. Hand
calibrated at the factory
3.
Would drift and could not be field calibrated
ii.
Digital
2. Relative
humidity accurate to +/- 5% over the range of 20% to 80%
3.
Enthalpy accurate to +/- 3Btu/lb. over the range of
20Btu/lb. to 36Btu/lb.
3. Repair vs. replace
The sense of those expert in economizers is that the
changeover sensors available for the older analog economizers cannot meet the
current ASHRAE 90, IECC or Title 24 requirements because of their design. They suggest that all analog economizers may
be considered as unacceptable because of their outdated design and their
well-established high failure rates.
a.
Replace analog sensor with a newer more accurate sensor
i.
Honeywell sensors
1. Enthalpy
old sensor - C7400A1000 – new C7400A2000
2.
Dry bulb – old sensor C7650 (10°F dead band) – new - C7660 (2°F dead band)
ii.
Part cost >$75 *2 (mark-up) +labor = ~$300 upgrade.
iii.
What does the customer get from this?
1. Replace
when there are humidity complaints. (Humid areas)
2.
Energy benefits expected
b.
Upgrade to a digital technology
i.
Experts have determined that the snap disk type
changeover is never acceptable.
ii.
Upgrade analog economizer with a digital sensor – If
replacing the change-over sensor always replace with the digital version even
if maintaining the analog economizer
iii.
Upgrading the economizer control, actuator, and sensors;
consider upgrading to digital economizer control, even when the analog
economizer appears to work if the unit is not old (less than 7 years old)
iv.
Upgrade the whole economizer to digital control when
the analog economizer appears to not work. Supply houses are phasing out analog
parts inventory, the service provider may only have a digital option.
4. There
are so many potential problems with analog economizers (i.e. sensor issues,
actuator reliability, damper leakage issues, linkage issues) is there a set of
circumstances where de-commissioning the failed economizer and going to a
manual outside air intake makes sense?
a.
Yes if the economizer has failed, the units is old and the
decision has been made to not repair it and there is a plan to replace it in
the next few years.
b.
No if the economizer is working, there is a comfort
problem and the assumption is that the outside air intake is contributing to
the comfort problem.
c.
No if the economizer is non-functional and the unit is
not old or does not have a replacement plan.
Economizer repair or replacement is suggested.
5. Experts
recognize that 2-stage temperature control of all units with economizers is a
requirement for proper operation.
6.
Real time economizer monitoring tools – The experts
consider the use of real-time economizer monitoring tools helpful if not
essential for validating analog economizer function in a service or
commissioning role but they are outside the scope of commercial maintenance.
7. It
is assumed that the technician will remove any jumpers and return the unit back
to normal operation when testing and maintenance is complete.
Challenges
1. Maintenance
is a fixed price activity. Some
economizers have access problems that make maintenance within the budget
challenging.
2.
The customers often don’t understand the economizer or
its value proposition. There currently is no data collected or metric available,
derived from maintenance inspection tasking that documents the performance of
the economizer.
The components
of an economizer
1.
Economizer logic control
2.
Wiring and associated connectors
3.
Mechanical connection from damper actuator to dampers,
which include gears, linkages, connecting rods, ball joints, and metal adapters
and associated fasteners
4.
Dampers
a.
Parallel blade
b.
Opposed blade
5.
Relief damper
6. Exhaust
fan or Power exhaust accessory
7.
Weather hood or eyebrow with filter/screen to prevent
precipitation, debris, and animals from entering the unit
8.
Outside air sensor
a.
Temperature or enthalpy
9.
Return air sensor, if set up for differential
changeover control
a.
Temperature or enthalpy
10. Mixed
and/or supply (discharge) air sensor
11. CO2
Sensor, if set up for Demand Control Ventilation
12. Remote
potentiometer - optional
13. Occupancy
Sensor - optional
14. Low
ambient mechanical cooling lockout
Economizer logic
(digital and analog economizers)
Suggested economizer maintenance
tasking
a - Check air filter and housing integrity. Correct as needed.
|
Quarterly
|
Understanding of the meaning of the task:
- Filter
fit refers minimizing air by-passing the filters because of gaps.
- Housing
integrity refers to “economizer hood” or “eye brow” and its ability to
seal out liquid moisture.
Guidance to technician when judging acceptable or unacceptable
condition or performance:
- Any
gap in the filters should be minimized.
If the gap is noticeable it should be filled.
- If
filter is damaged such that its performance is effected, it should be
replaced.
Guidance to the technician when performing the task:
1.
One common way to fill an excessive gap is with a metal
filler piece that may have to be fabricated.
Impact of unacceptable condition or performance:
1.
Filter bypass contributes to fouling return air filters
and evaporator coils. See this working
groups document about Table 5-22 for more information about the impact of dirty
return filters and a dirty evaporator.
2.
It a may also allow animals or moisture to enter into
system
3.
Moisture can cause corrosion on surfaces not
manufactured to protect against moisture, such as damper assembly, and may
damage electronic such as economizer control or sensors.
b - Check for particulate accumulation on filters. Clean or
replace as necessary to ensure proper operation.
|
Quarterly
|
Understanding of the meaning of the task:
1.
The work group understands this task relates to the outside
air air-filters in the economizer housing.
2.
The task is to inspect the filters for:
a.
Fit and seal in the frame
b.
Particulate accumulation that would restrict airflow
c.
Filter damage or disintegration that would allow liquid
moisture or vermin to pass
Guidance to technician when judging acceptable or unacceptable
condition or performance:
- When
working on units with metal mesh air filters, assessment means removing
the filter from the unit and looking at the amount of light that passes
through it. If it looks dirty, it is dirty.
Guidance to the technician when performing the task:
- The
work group recognized that it is a responsibility of the technician to clean
dirty economizer air filters.
- Economizer
filters are usually cleaned similarly to an evaporator coil, with a
detergent cleaner and water.
Impact of unacceptable condition or performance:
- Dirty
economizer filters restrict airflow and reduce the capacity of the
economizer to provide free cooling
- Dirty
economizer filters restrict airflow and reduce the capacity of the
economizer to provide ventilation air as needed
- Damaged
air filters may allow liquid moisture or vermin to enter the unit.
Best practices and minimum Standards:
1.
The sense of the Working Group is that economizer
filters should be cleaned at least annually as a minimum standard and that they
should be cleaned every time the condenser is cleaned.
2.
Best to clean counter to flow, providing water pressure
from damper side
c1 - Communicating economizers only - Check alarms,
review and document alarms, reset resolved alarms
|
Quarterly
|
Understanding of the
meaning of the task:
1.
This task is to review the alarms shown in the digital
economizer controller. All alarms should be documented. Alarms that relate to
conditions or performance that have been resolved should be cleared.
Guidance to
technician when judging acceptable or unacceptable condition or performance:
1.
There is no condition or performance issues related to
the alarm feature
Guidance to the
technician when performing the task:
1.
This task is part of every inspection when a digital
economizer is installed. All alarms should be documented. Persistent or
reoccurring alarms should be referred to service for resolution.
Best practices and minimum Standards:
1.
Documenting that an alarm has been resolved and what
was done to resolve the alarm is a best practice
2.
Reviewing previously documented alarms against current
alarms to uncover persistent or reoccurring alarms is a best practice.
c3 digital economizers only - Check condition, setting
and operation of outdoor sensor, return air sensor, or change-over controller
against a reasonable assumption standard. Repair, adjust, or replace
components to ensure proper operation.
|
Annual 2
|
Understanding of the meaning of the task:
1.
The changeover operation is one of the critical
operations of the economizer. This
task is to test and verify that economizer changeover sensors are reasonably
accurate and set to the desired set point, conditions permitting. There are two
annual tasks NOT intended to be performed at the same maintenance inspection.
2.
This task applies to both digital and analog
economizers.
Guidance to technician when judging acceptable or unacceptable
condition or performance:
1.
Analog Economizers – A simple test to determine the
accuracy of the outdoor air sensor when the FREE COOLING indicator does turn on
as described in conditions 4 & 5 in the analog economizer test procedure in
this document.
2.
Digital Economizers – Digital economizers have status
displays that show the current measured value for various sensors including
outside temperature and perhaps humidity, return air temperature and humidity,
mixed air temperature, supply air temperature and zone CO2.
Guidance to the technician when performing the task:
1.
Annual 1 – Validate the accuracy of the sensor against
a trusted instrument. See: Semi-annual inspection #1 (rigorous), one of the economizer
inspections each year (example: Fall)
2. Annual
2 – Validate the accuracy of the sensor against a reasonable assumption
standard. See: Semi-annual inspection #2 (cursory), a different one of the
inspection each year (example: Spring)
Impact of unacceptable condition or performance:
1.
Failure or inaccuracy of the changeover operation
greatly reduces the effectiveness on the economizer by missing free cooling
opportunities or by allowing excessive heat and humidity into the building that
then must be removed.
Timing for this task:
This task is appropriate for the
following maintenance visits
1.
Economizer inspection at heat and cool start-up.
d - Check condition, setting and operation of the economizer
controller and actuators. Repair,
adjust, or replace components to ensure proper operation.
|
Semi-Annually
|
Understanding of the meaning of the task:
1.
This task is to test and verify that economizer control
module and actuator is functional and controller settings are appropriate for
the application.
Guidance to technician when judging acceptable or unacceptable
condition or performance:
1.
A non-functional economizer control module is an
unacceptable condition and performance.
2.
Inoperable actuators are an unacceptable condition and
performance
Guidance to the technician when performing the task:
1.
Analog economizers - See the section about analog
economizer inspection and test procedures in this document.
2.
Digital economizers - See the section about
digital economizer inspection and test procedures in this document.
3.
Determining if the failure is a controller or actuator
problem is a service task
Impact of unacceptable condition or performance:
1.
Economizer controller or actuator failure disables the
economizer. This may cause excessive or insufficient indoor are for ventilation
and may have a large negative impact on system energy efficiency depending of
the position of the damper when failed and the indoor and outdoor climate
2.
Improper controller settings greatly reduces the
effectiveness on the economizer by missing free cooling opportunities or by
allowing excessive heat and humidity into the building that then must be
removed.
Best practices and minimum Standards:
1.
When checking the operation of the
controller/actuator/linkage, changing the minimum position setting is sometimes
required. If there is an assumption that
the minimum position setting is set correctly on arrival, marking the damper
shaft or marking the a measuring point on the dampers and recording the damper
opening when at the original minimum position so that the minimum position
setting can be reset to the original setting is a best practice
e1 analog economizers only - Check condition, setting and
operation of the mixed air/discharge sensor.
Repair, adjust or replace components to ensure proper operation.
|
Annual
|
e2a digital economizers only - Check condition, setting
and operation of the mixed air/discharge sensor against a trusted sensor. Repair, adjust or replace components to
ensure proper operation.
|
Annual 1
|
e2b digital economizers only - Check condition, setting
and operation of the mixed air/discharge sensor against a reasonable
assumption standard. Repair, adjust or
replace components to ensure proper operation.
|
Annual 2
|
Understanding of the meaning of the task:
2.
The mixed air/discharge sensor operation is used to
modulate the damper position to try to maintain the desired supply air
temperature. This task is to test and verify
that economizer mixed air/discharge sensor are reasonably accurate and are
controlling to the designed set point, conditions permitting.
Guidance to the technician when performing the task:
1.
Analog Economizers – To test the return air
sensor remove the outside enthalpy sensor from SO+ and SO and replace them with
the wires from the return air sensor. See: Verifying the functionality of
the changeover sensor and follow the procedure defined there.
It is critically important that the sensors are correctly
re-installed when testing is complete. The test described has the risk of
making a functional economizer non-functional by breaking terminals or wiring
during the test or by not leaving the sensors installed correctly when the test
is complete.
2.
Digital Economizers – Digital economizers have
status displays that show the current measured value for various sensors
including outside temperature and perhaps humidity, return air temperature and
humidity, mixed air temperature, supply air temperature and zone CO2.
Impact of unacceptable condition or performance:
1.
Failure or inaccuracy of the changeover operation
greatly reduces the effectiveness on the economizer by missing free cooling
opportunities or by allowing excessive heat and humidity into the building that
then must be removed.
Timing for this task:
This task is appropriate for the
following maintenance visits
1.
Economizer inspection at heat and cool start-up.
f - Check dampers for proper operation, condition, and setting. Repair, adjust, lubricate, or replace
components to ensure proper operation
|
Semi-Annually
|
Understanding of the
meaning of the task:
1.
Damper operation is a critical function of the
economizer. This task is to test and
verify that move in response to the actuator to lubricate the dampers and
linkages to maintain operability as well as to adjust the damper position to
produce the air flows intended by the controller.
Guidance to
technician when judging acceptable or unacceptable condition or performance:
1.
The Working Group suggests that the technician should
visually inspect fixed dampers and determine that they are positioned correctly
and if not adjust it or document the issue as per the requirements of the
maintenance contract.
Guidance to the
technician when performing the task:
1.
The Working Group recognizes that dampers may require
lubrication and have determined the lubricating dampers and linkages are a
required maintenance function.
2.
Verify dampers close tightly, verify and correct if
possible any damper seals that are damaged
3.
Technician can use potentiometer on analog units to
verify damper can open properly and remove G/N to see if the close properly
4.
Digital Economizers can use test to verify damper
opening and remove power to G to verify damper closes.
Impact of unacceptable
condition or performance:
1.
Improperly positioned fixed outside air dampers may
bring in excessive or insufficient outside air missing free cooling
opportunities or by allowing excessive heat and humidity into the building that
then must be removed.
g - DCV only - Check alarms, review and document
alarms, reset resolved alarms
|
Semi-Annually
|
Understanding of the
meaning of the task:
1.
All digital economizers and some analog economizers
have the ability to operate in DCV mode.
They need CO2 sensors and digital economizers sometimes need
to be set-up in software.
Guidance to
technician when judging acceptable or unacceptable condition or performance:
1.
When reviewing the status menu in digital economizers,
indoor CO2 should ventilate above 1000-1200ppm of CO2. If the CO2 reading is less than
300ppm or over 2500ppm the accuracy of the sensor is questionable.
Guidance to the
technician when performing the task:
1.
If the CO2 reading is below set point PPM
then verify that the damper position is at or near the CO2 min
damper set point. If CO2
value is above set point PPM, then verify that damper position is at or near
ventilation set point.
2.
If the CO2 sensor has a display, verify that
the sensor reading matches the CO2 reading on the controller
3.
Refer any problems observed for service
Impact of
unacceptable condition or performance:
1.
High CO2 is an indoor air quality problem.
It indicates that there is insufficient fresh air ventilation for building
occupants health and safety.
2.
Low CO2 is an energy efficiency
problem. It may indicate that the
building is over-ventilated. Outside air must be conditioned. Conditioning hot
and humid or cold outside air uses energy and adds additional load to the
systems that may compromise thermal comfort in extreme conditions.
Recommended
instrumentation requirements:
1. It is not expected that a maintenance
technician will have a CO2 measuring tool.
h - Check sealing integrity of all panels on equipment.
Replace fasteners and gasketing as needed.
|
Semi-Annually
|
Understanding of the
meaning of the task:
1.
This task refers to inspecting panel fasteners.
2.
This task refers to inspecting unit curbs and other
supporting structures.
Guidance to
technician when judging acceptable or unacceptable condition or performance:
1.
Panel fasteners – Panels should be secured with
fasteners.
a.
Missing fasteners should be replaced.
b.
Stripped fasteners should be replaced with oversized
versions or installed in an alternate locations.
2.
Panels – All panels should be in place when leaving the
job. Damaged or missing panels should be documented and recommended for
replacement.
Guidance to the
technician when performing the task:
1.
Be careful not to strip out the fasteners when reinstalling
them.
2.
Be careful not to drop panels on their corners, it may
puncture the roof and cause a leak.
3.
Document any holes or cracks in the curb, flashing or
surrounding roof and recommend repair.
4.
It is the technician’s responsibility to secure all panels
properly before leaving the unit.
Impact of
unacceptable condition or performance:
1.
Unplanned air leakage into or out of the unit is an
energy problem and the source of a potential comfort problem.
2.
Missing panels may cause a system reliability problem.
3.
Unsecured panels that blow off may be a liability problem
and a potential safety hazard.
Definitions:
1.
This task refers to inspecting all unit panels
including those that are structural, those that impact air leakage either in or
out of the unit, and those that are purely decorative.
2.
Fasteners are the means used to secure the panels to
the unit. They include screws, hinges,
latches or other devices.
i - Visually inspect areas of moisture accumulation for
biological growth. If present, clean or disinfect as needed.
|
Semi-Annually
|
Understanding of the meaning of the task:
1. This
Working Group determined that this task calls for a visual inspection and
documentation of unusual material without a determination of the identity of
the material.
2. This
Working Group determined that cleaning provides no assurance of any specific
outcome.
3. The
HVAC technician is very likely the only person that is going to look into the
HVAC unit on a regular basis and therefore must be relied on to note unusual
material.
Guidance to technician when judging acceptable or unacceptable
condition or performance:
1. The
Working Group recognizes that HVAC technicians are generally not trained to
identify biological growth.
2. The
technician is encouraged to document, with a photograph if possible any unusual
substance found in the unit.
Guidance to the technician when performing the task:
1. The
Working Group determined that the technician has the responsibility to document
the existence of anything unusual in the unit.
Impact of unacceptable condition or performance:
1. Unusual
substances may be a concern to the building occupants.
Definitions:
1. Unusual
means that which the technician determines is not ordinary.
Best practices and minimum Standards:
1. It
is a best practice to document unusual substances with a photograph.
j - Check condition, setting and operation of the low limit
stat. Repair, adjust, or replace
components to ensure proper operation.
|
Annually
|
Understanding of the
meaning of the task:
1.
This task is to verify the operation of the outside air
thermostat that disables mechanical cooling operation below the set-point
regardless of any temperature control signals.
Guidance to
technician when judging acceptable or unacceptable condition or performance:
1.
Mechanical cooling operation during low ambient
conditions when a low ambient lock out stat is installed is an unacceptable
condition
Guidance to the
technician when performing the task:
1.
Checking the low limit or low ambient lockout stat
requires low ambient conditions. This
task may be included in the winter mid-season inspection when low ambient
conditions exist. The test would be to
produce a 2-stage call for cooling and verifying that mechanical cooling does
not operate.
Impact of
unacceptable condition or performance:
1.
Unadapted mechanical cooling operation during low
ambient conditions is a hazard to the compressor
2.
Running mechanical cooling during low ambient
conditions when an economizer is installed may unnecessarily use energy
k - Check condition, setting and operation of the relief
dampers or power exhaust fan. Repair,
adjust, or replace components to ensure proper operation.
|
Annually
|
Understanding of the
meaning of the task:
This task is to verify the operation of the relief dampers
or power exhaust accessory
Guidance to
technician when judging acceptable or unacceptable condition or performance:
Barometric dampers, if existing must operate freely
Power exhaust accessories must operate according to the
economizer sequence of operation
Guidance to the
technician when performing the task:
Power exhaust accessory fans must operate at some point
prior to the economizer reaching 100% outside air. When it begins to operate is application
specific.
Impact of
unacceptable condition or performance:
Inoperable relief dampers or power exhaust accessories may
cause the building to be over-pressurized during economizer operation.
Inoperable relief dampers or power exhaust accessories may
cause the zone to insufficiently ventilated for indoor air quality or free
cooling.
I simply discovered this online journal and have high trusts in it to proceed. Keep up the considerable work, its elusive great ones. I have added to my top picks. Much obliged to You. Synergy Companies
ReplyDeleteA very informative article it was. Now a days heating repairing problem getting a big issue. I think we can solve some issue through this post. Thank you so much.
ReplyDeleteI can see that you are an expert at your field! I am launching a website soon, and your information will be very useful for me.. Thanks for all your help and wishing you all the success in your business. look at this site
ReplyDeleteI like this post,And I figure that they having a great time to peruse this post,they might take a decent site to make an information,thanks for sharing it to me
ReplyDeletebuy general ac price in uae
It is unfortunate that a majority of times roofs on commercial buildings are often ignored until there is a large problem, such as a leak, missing shingles, or water clinging to the ceiling of the commercial building. commercial roofing Toronto
ReplyDeleteI recently came across your blog and have been reading along. I thought I would leave my first comment. I don't know what to say except that I have enjoyed reading. Nice blog. I will keep visiting this blog very often. Advanpro furnace cleaning
ReplyDeleteNice article, Which you have shared here about the HVAC maintenance. Your article is very informative and useful to know more about the process of HVAC maintenance. Thanks for sharing this article here. Expert HVAC services Houston
ReplyDeleteQuote for ac unit cost of replacement This particular is usually apparently essential and moreover outstanding truth along with for sure fair-minded and moreover admittedly useful My business is looking to find in advance designed for this specific useful stuffs…
ReplyDeleteThis comment has been removed by the author.
ReplyDeleteThis comment has been removed by the author.
ReplyDeleteI am pleased that this article provided me with some important information. Thank you so much for sharing it. Keep up the good work. toledo hvac companies
ReplyDeleteI'd like to express my gratitude for writing such an informative piece on this blog. This article provided me with a variety of data. Continue to post. appliance repair
ReplyDeleteGreat job for publishing such a nice article. Your article isn’t only useful but it is additionally really informative. Thank you because you have been willing to share information with us. Read more info about Heating Air Conditioning Service in USA
ReplyDeleteThanks For this blog sharing
ReplyDeleteAircon service
I really loved reading your blog. It was very well authored and easy to understand. Unlike other blogs I have read which are really not that good.Thanks alot! HVAC maintenance contracts
ReplyDeleteYou have done good work by publishing this article here.AMGO 4 Post Lift I found this article too much informative, and also it is beneficial to enhance our knowledge. Grateful to you for sharing an article like this.
ReplyDeleteGreat job for publishing such a nice article. Your article isn’t only useful but it is additionally really informative. Read more info about hvac cleaning services chicago. Thank you because you have been willing to share information with us.
ReplyDelete