The Diagnostic Method
This diagnostic method is a generally accepted diagnostic
method used by the HVAC industry. Measuring temperatures and pressures and
doing calculations and comparing the outcomes of the calculations to what are
acceptable operating ranges is what makes the technician skilled in
refrigeration cycle diagnosis.
What are acceptable operating ranges for the important
performance indicators, evaporating temperature, superheat, subcooling and
condensing temperature over ambient? There is a wide variation in the outcomes
of the diagnostic methods used by skilled technicians because of differing
opinions as to what is an acceptable operating range, what is the meaning of an
indicator and what are the standard service procedures used by the company or
the technician. There are technologies
available to help. Selecting a
technology that has been tested by an independent third party is important.
Some objective criteria when determining acceptable
operating ranges
Evaporating temperature- If the evaporating temperature gets
much below 32°F, the
condensate on the coil can start to freeze.
If the evaporating temperature gets much above 47°F, the system is very likely to not control
humidity. A low efficiency unit under
low load may have an evaporating temperature goal near 32°F and a high efficiency unit
under high load could have an evaporating temperature goal at the upper
range. Keep the coil cooler if humidity
control is important and try to maintain higher evaporating temperatures when
humidity control in unimportant
Superheat- High and low superheat leads directly to
premature compressor failures. With
fixed orifice equipment, the superheat expectation is found on the units
charging chart. Expect higher superheat
goals when it is cool outside or when there is a large load inside. With TxV equipment, the superheat expectation
is around 20°F
Condensing temperature over ambient- Normally expect the COA
to be under 30°F.
Higher efficiency units have lower COA expectations. The COA expectation of fixed orifice
equipment is strongly influenced by the load on the evaporator. Low COA is an indication that relatively
little heat was absorbed on the low side.
Subcooling- Subcooling is the best way to charge TxV
equipment. The subcooling goal for TxV
equipment is a manufacturer provided value. If the manufacturer’s specification
is not available, the generally accepted best guess is 10°F. The normal range across all makes and models
is 5°F to 20°F. That is not to say that anything between 5°F to 20°F is acceptable, but that
there is equipment where the goal is 5°F
and others that have goal values as high as 20°F. With fixed orifice equipment, subcooling is
useful in troubleshooting, but the expected value is not stated.
The expected values for the performance indicators
evaporating temperature superheat, condensing temperature over ambient and
subcooling given above cannot be considered precise for any individual
machine. The range of acceptable
performance for low efficiency equipment at low loads has no overlap with the
range of acceptable performance values for high efficiency equipment under high
loads. I use a technology developed by
my company, Field Diagnostic Services Inc. (https://www.fielddiagnostics.com/). There are other methods used by other
people. Independent third-party research
has proven that not all fault detection and diagnostic methods are equally
effective. The task of considering all the variables that go into determining
acceptable goal values is probably not something people can do without a
technological tool.
Diagnostics
If you can achieve the superheat and subcooling goals within
an acceptable range of evaporating and condensing temperature, the system is
likely to operate dependably over a wide range of conditions. Use fault
detection and diagnostics when the superheat and subcooling goals cannot be
achieved within the limits of acceptable evaporating and condensing temperature.
There is an alternate concept of superheat and subcooling
that can be useful when puzzling out refrigeration cycle problems.
An alternative concept of superheat is that superheat is the
relative amount of refrigerant on the low side, given the heat transfer
capacity of the evaporator. What does that mean? It means that if you want to lower the
superheat you can add refrigerant, or you can lower the heat transfer capacity
of the evaporator. How would a technician lower the heat transfer capacity of
the evaporator? A technician can lower the heat transfer capacity of the
evaporator by reducing the fan speed or restricting the airflow in some way..
An alternative concept of subcooling is that subcooling is
the relative amount of refrigerant on the high side, given the mass flow rate
of the refrigerant through the system. What does that mean? It means that if
you want to raise the subcooling you can add refrigerant, or you can restrict
the mass flow rate of the refrigerant through the system. How would a
technician restrict the mass flow rate of the refrigerant through the system?
While some technicians rightly point out that adjusting the expansion valve is
a way of adjusting the mass flow rate, most technicians understand that it
takes a greater than ordinary amount of skill and time to effectively adjust a
TXV, and that is often not the answer to the problem anyway. The TxV is a
superheat controller and should be adjusted to the superheat goal and not be
used to adjust subcooling. Having said
that, an expansion valve that has be miss-adjusted to stay open may not allow
subcooling to become established, almost regardless of how much refrigerant is
added to the system.
Technicians don’t generally add restrictions to a system as
a service procedure. However excessive restrictions to refrigerant flow are
characterized by high subcooling in combination with high superheat and low
evaporating temperature. What this leaves
us with is that when considering the level of charge in a system, subcooling is
driven by adding and removing charge.
So, if working on a TXV system, charge to achieve the
desired subcooling and then adjust the fan speed to get the superheat correct. When
working on fixed orifice equipment, set the fan speed and charge by superheat.
When doing fault detection and diagnostics, the conditions
we are left with is superheat can be high and superheat can be low and
subcooling can be high and subcooling can be low.
Some examples
Let’s consider the case where the subcooling is high and the
superheat is also high. If we apply the alternate idea about subcooling, we see
that when there is high subcooling, there is a lot of refrigerant on the high
side backing up into the condenser; when we add the alternate superheat idea we
see that when the superheat is high, there isn’t much refrigerant on the low
side. A technician may think of this as an undercharged low side and an
overcharged high side.
What kind of problem would we have if the system has a lot
of refrigerant on the high side and not much on the low side?
Refrigerant flow restriction
In order for an air conditioner to operate properly,
refrigerant flow through the metering device (which ultimately is capacity)
needs to match the amount of heat absorption capacity of the evaporator and it
needs to keep up with the pumping capacity of the compressor.
The diagnostic method described here is more sensitive to
restrictions than the commonly held belief that refrigerant flow restrictions
cause a temperature drop at the point of the restriction. It’s true that if the restriction is severe
enough to result in a pressure drop large enough to cause the refrigerant to
start to flash, or become a vapor, a temperature drop will be noticeable. With a more sensitive detection method,
restrictions will be diagnosed that will require a decision about when and
whether to fix the restriction. Sometimes, with relatively minor restrictions,
it’s better to overcharge the system, raising the head pressure and increasing
the flow through the restriction a bit and live with the slight restriction because
the cost to repair restrictions is high. Restrictions cause reduced capacity
and reduced efficiency of the system.
Severely restricted refrigerant flow makes it impossible to
have enough flow to pressurize the evaporator (low suction pressure). Restricted
refrigerant flow makes it impossible to cool down the suction line (high
superheat).
Under-charged
Another case where the superheat is high is when the system
is under charged. This time however, the
subcooling is low. Using the alternate ideas of superheat and subcooling, low
subcooling means a lack of refrigerant is on the high side. High superheat
means too little refrigerant on the low side. What would cause that? A
restriction causes the superheat to be high by not allowing the refrigerant in
the system to flow into the evaporator and causes the subcooling to be high by
filling the condenser with the refrigerant.
When the system is undercharged, the superheat is high for the same reason;
the refrigerant is not flowing into the evaporator. The difference is that the reason is for the
refrigerant flow problem is the fact that there is just not enough refrigerant
in the system, as confirmed by the low subcooling calculation.
Under-charge can cause greatly reduced system capacity but
it has a smaller effect on the reduction in efficiency of the system because
under-charged systems have very low head pressure.
Very low refrigerant mass flow because of under-charge also
makes it impossible to have enough refrigerant flow to pressurize the
evaporator (low suction pressure). Low refrigerant flow again makes it
impossible to cool down the suction line (high superheat). This time however,
the subcooling is also low.
Over-charged
This is the case when the superheat is low and the
subcooling is high. Using the alternate ideas of superheat and subcooling, high
subcooling means a lot of refrigerant is on the high side. Low superheat means
too much refrigerant on the low side. What would cause that?
Excessive refrigerant charge fills the condenser with
refrigerant resulting in high subcooling and high condensing temperature over
ambient, or as technicians would say “high head pressure”. Excessive high side pressure increased the
pressure drop across the metering device.
This over-feeds the refrigerant into the evaporator and over-cools the
suction line. This will be seen as low superheat.
Overcharge has a much smaller impact on capacity, but the
elevated high side pressure caused by overfilling the condenser with
refrigerant increases the amount of energy used by the compressor to pump
against that high head pressure; thus reducing system efficiency.
Low side heat transfer problem, miss-matched equipment or an
overfeeding metering device
That leaves us with the last case; low superheat and low
subcooling. The system with low subcooling is undercharged, however a system
with low superheat it is running too cold on the low side. You can’t remove
charge, as you might want to do to raise superheat, because the subcooling is
already low and you can’t add charge to raise the subcooling, because the
superheat is low. Maybe charge isn’t the first issue that needs to be dealt
with here.
Low side heat transfer problem
The refrigeration cycle cannot tell why there is
insufficient heat being absorbed. It
might be that there is not enough air flowing across the evaporator. That may be caused by the fan running too
slow. It also may be caused by a
restriction to airflow caused by dirty filters.
Airflow can be restricted by undersized ductwork or too few return or
supply grills. There may be dampers in
the ductwork that are closed. A dirty
evaporator coil also causes the system to absorb too little heat given its
refrigeration capacity. The dirt on and
inside the evaporator not only restricts air flow, but dirt is also an
insulator. Insulators are not desirable
in a heat transfer system.
A low side heat transfer diagnosis is the proper diagnosis
whenever the evaporating temperature is low and the superheat is low, without
regard to subcooling. When the
subcooling is also low, this just indicates that a previous technician tried to
resolve the low superheat condition by removing charge and then leaving the job
without solving the problem.
Low superheat and low subcooling is not a single problem. It
is called a “multiple coincidental faults” situation. Meaning that more than one fault exists at
the same time. Some would argue that
nearly every system has this condition.
When the fault or combination of faults become severe enough to be
noticeable as a comfort problem, or has the performance indicators out of
acceptable ranges they must be dealt with.
Solving multiple coincidental faults
Since all systems may have multiple coincidental faults at
some level, the resolution is to break the problem up into pieces. The principle I would propose is to do the
maintenance activity first, then make adjustments, and if that isn’t effective,
you’re left with a hard fault.
Do your maintenance first
This means if heat exchangers, the evaporator and condenser
are fouled, clean them. If the fan has a
belt drive, check the belt and sheave for wear, replace dirty filters. Make sure the condenser fans are running and
running in the right direction. Doing your maintenance first is an important
principle. It starts the process of
actually solving the problem, instead of just covering it up or adapting the
system to the problem.
Then make adjustments
This means that when the fundamentals are resolved and the
system can operate properly, make the necessary adjustments to the system so it
does run properly. This means if the
subcooling is low, add charge. If the
subcooling is high, remove charge. When
the subcooling is correct, meaning something like the right amount of
refrigerant is in the system, there still might a superheat or evaporating
temperature or condensing temperature over ambient problem. At least you know it’s not a charge problem.
Then tackle the next issue.
If the condensing temperature over ambient is high, look into the
condenser fans and look at the condenser again.
Some condenser coils have two or ever three condenser coils sandwiched
together. They need to be split apart to
clean them. If the superheat is still
low, look into the air flow. Does the
fan need to run at a higher speed? Is
there dirt crusting the blower wheel? Is the ductwork adequate?
There is a situation that rarely occurs but can happen. This is when no matter how much refrigerant
you add to the system, no subcooling is established. This can be a real puzzler if you never saw
it before. In that case, the refrigerant
flow through the metering device must be so excessive that no liquid can stay
in the condenser. In a correctly
designed system with an adjustable TxV, the TxV may be adjusted to almost no
spring pressure allowing the valve to stay wide open all the time. Adjust the TxV to attempt to resolve
that. We will discuss adjusting the TxV
in the next installment of this series.
Hard faults
If the fundamentals are right and adjustments aren’t solving
the problem, there may be a hard fault.
Hard faults are problems that are only resolved by replacing
something. There are three common hard
faults. The compressor can be
inefficient, the can be a refrigerant flow restriction or there can be
non-condensables, or contaminants in the refrigerant.
Inefficient compressors
Inefficient compressors or compressors with broken pistons
or valves will have very high suction pressure and low head pressure. If an inefficient compressor is suspected, do
an efficiency test by closing a valve and stopping refrigerant flow while
running the compressor. If the
compressor has a suction service valve, use that. Otherwise close the liquid
line valve. If no valves are available
the efficiency test cannot be performed.
With the valve closed an intact compressor will pump down into a
vacuum. Many technicians like to see the
compressor pull down to 20 inches of vacuum.
When the compressor pumps down, shut it off. The intact compressor will hold the suction
side vacuum. If the compressor does not
pump down or hold the vacuum the cause may be an inefficient compressor.
There are exceptions to this that must be investigated
before arriving at a final diagnosis. A compressor that has cylinder head
unloading or hot gas bypass unloading is designed to reduce its pumping
capacity. Those systems must be disabled
prior to testing. If the compressor
pumps down, but the low side pressure slowly rises, pump it down again.
If each time you pump it down the pressure rises more slowly
and raises less, you are very probably pulling refrigerant entrained in the oil
out. This means the compressor was
slugging, meaning liquid refrigerant was entering the compressor. Continue to pump the system down to “clean”
the liquid out of the oil and then find the root cause of the low superheat
operation.
Non-condensables
Non condensables are materials that contaminate the
refrigerant. Common non-condensables are
air, nitrogen and water. The most common
cause of non-condensables is sloppy service and installation procedures. A system must have the air removed from it
with a vacuum pump prior to charging.
Proper evacuation procedures include replacing the oil in the vacuum
pump prior to use on each system and using a vacuum gage to measure that a deep
enough vacuum was achieved. Detailed
evacuation procedures are a topic in themselves.
Testing for non-condensables means having the all
refrigerant in a system, to the extent possible, at the saturation temperature.
This means the system should have not been operating for long enough that the
liquid line is at the ambient temperature, and in the case of split systems,
the evaporator coil is at return air temperature. When that condition exists, measure the
suction line temperature and suction line pressure and compare them to what the
T-P chart says it should be. Almost all
contaminants in refrigerants have higher vapor pressures than refrigerant. If the pressure in the system is higher than
the chart says pure refrigerant will be at that temperature, there are
non-condensables in the refrigerant.
Take measurement errors into consideration. The rule I use is that if the pressure
measured corresponds to a temperature 3°
or higher than the current measured temperature, non-condensables are confirmed
to a level significant enough to cause a high head pressure condition.
Restrictions
High superheat and high subcooling indicate a restriction to
refrigerant flow. The problem is
determining where the restriction is.
The most common places for a restriction are the liquid line drier or
the metering device. From a contractor’s
business perspective, since the cost of removing the refrigerant, evacuating
and re-charging is so high, the prudent course of action is just to replace
them both when that is practical. There
are many good reasons what that might not be practical in any given case, but
replacing one without the other increases the risk of spending all that time
and money and not resolving the problem.
Refrigeration cycle diagnostics requires collecting the six
important measurements.
SP - suction pressure
LP - liquid pressure
ST - suction temperature
LT - liquid temperature
AMB - outdoor ambient
temperature
RAWB- return air wet bulb
temperature
From these measurements we can
calculate these performance indices:
COA (condensing temperature over
ambient)
ET (evaporating temperature)
PD (pressure drop across the
metering device)
SH (suction superheat)
SC (liquid subcooling)
The problems a working technician
sees most commonly.
1. There can be too little heat absorbed
into the low side.
2. There can be too much heat absorbed
into the low side
3. It can be too hard to reject heat from
the high side.
4. There can be too much heat rejected
from the high side
5. There can be too little refrigerant in
the system
6. There can be too much refrigerant in
the system
7. There can be too little refrigerant
flow through the system
8. There can be too much refrigerant flow
through the system
9. There can be contaminants in the
refrigerant
10. The compressor can be pumping less
than it was designed to
An effective diagnostic method
eliminates the need to guess and produces reliable and efficient HVAC units.
Share wonderful details concerning your blog, Blog truly useful for us. Commercial General Contractors Near Me
ReplyDeletek;
ReplyDeleteAwesome! No words. You always go one step beyond.
ReplyDeleteThere is so much great, useful information here. Thank you! Thank you! Thank you!
Read our guide if you wish.
besttoolsbrand
Thanks again :)