Refrigerant and the Compressor
Every day technicians put their gauges on air conditioners
and measure the high and low side pressures. Why do they do that? We know that
we need the pressure information to make decisions about how well the unit is
running and if there is anything we need to do to help it run better. But did you ever stop and think about why you
measure those pressures, and exactly which pressures you are measuring?
There are only few reasons to care about the refrigerant
pressures in the system. One is to estimate the saturation temperature of the
refrigerant. This is because most of the
calculations we make to determine the operational state of the refrigeration
cycle compares the saturation temperature to the pipe temperatures or the
ambient temperature. We need to measure the high and low side pressures in
order to know the saturation temperatures, however once we have that, the
measurements, calculations and rules will be in temperature and the pressure
information has little further use.
There is another slight complication, the high-side pressure we need is
the liquid pressure. Sometimes in
package equipment there may not be a convenient liquid port and you will have
to use discharge pressure.
Important- The liquid pressure and the discharge pressure
are not the same. There is a pressure
drop across the condenser coil. When you
have discharge pressure, you have to estimate the condenser pressure drop to
arrive at an approximation of liquid pressure.
This guess will add an error to the subcooling estimate. That error may be small or it may be great
but it will be there. We will discuss
this further when discussing the condenser.
Saturation Temperature
What is saturation
temperature? It’s the temperature a pure
stable mixture of vapor and liquid refrigerant will be at a given pressure.
That relationship is documented on the TP chart that is used to characterize
the refrigerants. In an air conditioner,
the low side saturation temperature is called the evaporating temperature. It
can be thought of as the temperature at which the liquid refrigerant evaporates
into a vapor. The high side saturation temperature is called the condensing
temperature and it’s the temperature at which the refrigerant vapor returns to
its liquid state.
The Temperature-Pressure Chart
What does the TP chart tell us? The T-P chart tells us the
saturation temperature of the various refrigerants over the range of
refrigerant pressures the technician is likely to see. You will often find
temperature scales printed on the refrigerant gauge face; those are a version
of the T-P chart.
What does saturation mean?
It means that there is both liquid and vapor present. It can be thought
of as the temperature at which the refrigerant is changing state in an air
conditioner. The refrigerant is flashing off at the evaporating temperature
deduced from the low side pressure. And the vapor condenses back into a liquid
at the condensing temperature that is derived from the liquid pressure.
What other criteria must be met for the T-P chart to be
reliable? Aside from the presence of both liquid and vapor refrigerant
together, the system must be at a stable temperature and contain it must
contain pure refrigerant. Nearly all substances that contaminate refrigerant
will have a higher vapor pressure than pure refrigerant, so the pressure of
contaminated refrigerant will nearly always be higher than the T-P chart’s
value at a given temperature.
Again, saturation temperature is interesting because the
calculations we will make to determine whether or not the unit is running
correctly have us comparing the saturation temperature to the pipe temperatures
and to the ambient temperature. There are no pressures in any of these
calculations.
For more information about using T-P charts, see:
Thinking in Temperature
I found that when I stopped thinking in terms of head and
suction pressures, and started thinking in evaporating temperature and
condensing temperature, I started to “get“ the refrigeration cycle. I never
really did before that. One advantage of thinking in temperature becomes clear
when working with different refrigerants.
There is no important difference between a 40°F evaporator with R22 and
a 40°F evaporator with R410A, or any other refrigerant, other than the trivia of
what the pressure measurement is.
What is Superheat?
Superheat is any temperature over the saturation
temperature. It means that if we are measuring a suction pressure that converts
on the T-P chart to a 40°F evaporator and the temperature of our suction line
near the compressor is 60°F then we have 20°F of total superheat entering the
compressor. Superheat is how much warmer the refrigerant is than when it
evaporated. When you have sufficient superheat,
you expect that the refrigerant entering the compressor is all vapor. That’s
important because when liquid refrigerant enters the compressor, it can damage it.
Why Do We Care About
Superheat?
In comfort cooling, the primary reason to care about
superheat is to protect the compressor from harm. High and low superheat leads directly to
premature compressor failures. It’s not
possible to predict how long a compressor with high or low superheat will run,
but if you keep your superheat at an acceptable level, your rate of compressor
failures will be reduced.
Causes of Compressor Failure
Let’s review the ways that compressors can fail. There are
mechanical failures and there are electrical failures. Mechanical failures are
inefficient compressors and locked rotor compressors. Electrical failures
include open and shorted motor windings, with and without acid. There are other
types of compressor failures (an example might be leaking motor terminals) but
these are, by far, the most common ways compressors fail. Did you know that the
manufacturers tell us that between a third and a half of all compressors
returned under warranty have no detectable fault? Those are big numbers. It shows us that technicians, on average are
not perfect at condemning compressors.
Locked Rotor Compressors
A common problem diagnosis is a locked rotor
compressor. What would you do to
diagnose a locked rotor compressor? It would probably start with a no-cooling
call, a locked rotor compressor won’t start and run when it’s energized and it
gets hot and it hums. Measure the current drawn by the compressor with a
current meter and if it is very high, many technicians would assume they have a
locked rotor compressor.
But does it prove you have a locked rotor compressor? No,
what you really have to do is to see what the LRA (locked rotor amperage)
rating is if you suspect a locked rotor compressor. The compressor nameplate
says what the LRA is, that is the current that would be drawn by the compressor
if it has a locked rotor. If we are measuring LRA with a current meter, we have a locked rotor
compressor. If not, there is probably
another problem.
What if the compressor is not pumping, it’s getting hot, and
it’s pulling a lot of current but less that LRA? If it’s a three-phase
compressor, it might be single phasing and if it’s a single phase compressor it
might have a bad capacitor or potential relay.
It’s important to be careful when condemning a compressor. On
3 phase I check current on all three legs, if one is pulling close to zero
amps, it single phasing. You may also check
for voltage on all three phases at the compressor motor terminals before
condemning a compressor as locked rotor. It might make more sense to replace a
contactor or a wire or a fuse instead of the compressor. On single phase equipment, checking the
capacitor and starting components and the wiring to the compressor makes sense.
It’s important to know what causes compressors to fail
because it can help you make a more accurate diagnosis and because, if you know
the kinds of things that cause particular compressor failures you can take
steps to make sure the new compressor doesn't fail the same way.
What is a Locked Rotor Compressor?
The rotor is the part of
the compressor/motor pair that turns. A locked rotor compressor would be one
where those parts will not turn.
What Caused Locked Rotor Compressors?
“Slugging” or the
introduction of liquid refrigerant into the crankcase of the compressor is a
common cause of locked rotor compressors. To think of it another way, it is often
caused by compressors being forced to run with low superheat.
Liquid refrigerant is a highly effective degreasing solvent.
When liquid refrigerant is in the crankcase of a compressor, it dissolves the
oil. When the oil pump picks up the refrigerant-laden oil, sometimes the heat
of compression in the pump is enough to flash off the liquid. That creates a
bubble of gas that forces the oil down the dip tube and starves the pump for
oil. The main bearings then run dry until they seize from lack of lubrication.
Another scenario is when the liquid refrigerant is actually
pumped into the bearings. There it cleans away any lubrication and the
compressor locks up. In either case, low superheat is the cause.
Inefficient compressors
What is an inefficient compressor? Generally when we think
about efficiency we think about the capacity of something over the power used
to achieve that capacity. That is not the kind of efficiency we are talking
about when calling a compressor inefficient. A compressor is a pump. When engineers
think about the compressor in a refrigeration cycle design, they are thinking
about Cubic Feet per Minute (CFM) of pumping capacity. That capacity is equal
to the volume of the cylinders multiplied by the number of cylinders working
together further multiplied by the number of times the motor turns the
crankshaft each minute. When the compressor delivers fewer CFM in pumping
capacity than it is rated for it is considered volumetrically inefficient.
Technicians are quick point out that volumetric inefficiency is the result of
broken valves, pistons and piston rods.
What causes an inefficient compressor?
Liquid refrigerant that enters the crankcase can get pulled into the cylinder heads along with the vapor. Liquid refrigerant is uncompressible in refrigeration compressors; the materials that the valves and pistons are made of were not designed to stand up to the kind of force needed to compress a liquid. When they are subjected to that condition they fail and break into pieces. A compressor without its pistons or valves pumps less than it is rated to with all its pistons and valves intact.
Liquid refrigerant that enters the crankcase can get pulled into the cylinder heads along with the vapor. Liquid refrigerant is uncompressible in refrigeration compressors; the materials that the valves and pistons are made of were not designed to stand up to the kind of force needed to compress a liquid. When they are subjected to that condition they fail and break into pieces. A compressor without its pistons or valves pumps less than it is rated to with all its pistons and valves intact.
Liquid refrigerant in the compressor causes inefficient
compressors, low superheat risks liquid refrigerant entering the compressor.
Open or Shorted With Acid
Electrical failures in a compressor are often caused by
mechanical failures in that compressor, but without an intact motor there is no
way to see it.
What Causes Electrical Failures With Acid?
A common answer
from technicians is that moisture in the oil causes acid. That is not the case.
What causes acid in refrigeration systems? In systems with
R22 and mineral oil, acid formation is primarily due to the thermal degradation,
or overheating, of the refrigerant; this results in the formation of
hydrochloric and hydrofluoric acids. These are strong mineral acids. The oil
lubricants used in the older systems were relatively stable and were not prone
to hydrolytic degradation due to the low solubility of water in oil.
Excessive heat inside a compressor can come from external
power problems like single phasing and low voltage. It can come from internal
problems like a locked rotor compressor cycling on the thermal overload for an
extended period of time or a system without a head pressure switch internally
bypassing hot gas into the crankcase when operating with extremely high head
pressure.
The refrigeration cycle maintenance problem that causes high
temperatures is running with high superheat. In a hermetic or semi-hermetic
compressor the motor often counts on there being enough cooling capacity in the
returning suction line gas to cool the motor windings. When there isn't enough
cooling capacity in the suction gas, the motor temperatures rise to the point
where the high temperatures degrade the refrigerant. The high temperatures also degrade the
insulation on the motor winding causing them to short out. The two effects are usually coincidental; one
does not usually cause the other. An exception to that might be that acidic
refrigerant will also degrade motor winding insulation. That may be the cause
of a second burnout if effective acid neutralization of the oil is not
performed as part of the replacement procedure.
When a burnout occurs, the system needs to be cleaned up or
the acid will destroy the new compressor. It’s equally true that the high
temperature condition that caused the original burnout must also be corrected
for the system to continue in operation.
Open or Shorted Without Acid
What Causes Electrical Failures Without Acid?
Motor winding failure without acid is traceable to physical
damage or an intentional disruption of continuity through the motor windings, like
an open thermal overload. Running with low superheat may result in broken
pistons and valves. Pieces of broken
pistons or valves may damage motor windings. High temperatures caused by locked
rotor or single phasing or running with high superheat. This may cause the thermal
overload to open
Compressors generally don’t wear out. They are often killed by
being forced to run under conditions that inevitably lead to their failure. Those
conditions are high or low superheat. Controlling superheat is an
important part of the service technicians’ job. Controlling superheat is almost
all about saving the compressor in comfort cooling applications.
The compressor nameplate says what the LRA is, that is the current that would be drawn by the compressor if it has a locked rotor. deshumidificadores
ReplyDeleteRefrigerant leak tracking in refrigeration and air-conditioning (RAC) units and heating, ventilation and air conditioning (HVAC-R) systems is very difficult, even for the most experienced heating and cooling technician. The leak could be well hidden from view in tubing, a system component, or in an operating or safety control component. home improvement contractors
ReplyDeleteThanks for sharing about the construction. It will be beneficial for us. Looking for the reliable services for your home improvement, then you can visit on reliance construction
ReplyDeleteShare wonderful details concerning your blog, Blog truly useful for us. Commercial General Contractors Near Me
ReplyDeleteThanks for sharing the informative stuff.It was very useful to know the functions of refrigerants and compressor.
ReplyDeleteGreat work man you have to post a great post it will help people very much keep it do more for people like that https://anjun1.net/
ReplyDeleteThanks for sharing the best information and suggestions, I love your content, and they are very nice and very useful to us. If you are looking for the best ac in India,then Budget Kart.I appreciate the work you have put into this.
ReplyDeleteThis comment has been removed by the author.
ReplyDeleteYou shaped this article carefully about Generator. It's significant for me yet also crucial for other people who are looking for this data. Appreciative to you for sharing this great information. emergency breakdown service compressor
ReplyDelete