INTRODUCTION
In buildings supplied from central
plants, one service responsibility is the air handler that is used to condition
the space, the control system and the piping, usually to the main hot water and
chilled water supply and return piping.
The air handler is a box with a fan
and motor, supported on spring mounts, helping to isolate the vibration to
within the machine, and not transmit it to the building structure. The components in the box may include an
economizer, filters, hot water, steam and/or chilled water coils, and a
condensate pan and drain system. Please Press "Read More"
Controls
There could be several semi
independent control systems for it or a single controller integrated into a
building management system.
The Economizer
The economizer is an outside air
duct and damper intersecting with the return air duct and damper and its
controls and actuators. It is used to
cool the conditioned space with outside air when cool outside air is
available.
The hot and chilled water coils come
after the economizer and filters.
The Chilled Water Coil
The chilled water coil is thick,
commonly six passes. A four-pass coil
may be incorrect. If you see one, and
there is a need for additional capacity, check with the plans to see what was
specified. Four-pass coils in place of a specified six-pass coil will have a
low ΔTw and a low ΔTa. See that the supply water enters the air leaving side of
the coil. This is an important capacity issue, the coldest water should
interact with the coldest air.
The Hot Water or Steam Coil
The hot water or steam coil is often
first in the air stream, after the economizer and filters. If it is not, ask
the question about that and get clarification.
If it is installed wrong, and that is something that happens, it may
become a freeze hazard. The hot coil is
usually thin, typically one or two passes.
This is because of the greater ΔT between the hot water and the air,
than the chilled water and the air.
Additionally, the internal heat gain in the buildings, often primarily
from the lighting is subtracted from the heating load, while it is added to the
cooling load. It is first because it
freezes more slowly and protects the chilled water coil.
The Condensate System
The condensate system catches the
water that condenses on an active chilled water coil. It then carries it away from the unit and
disposes of it properly. The system
consists of a pan that the chilled water coil sits in. It has a drain connection on one side. When the unit is level, the drain side of the
pan is the low side. There is a trap in
the drain line. The trap prevents the
negative pressure of the fan from pulling air through the condensate line. When the unit runs without a trap the fan
sucks air through the condensate drain.
This prevents the water from leaving the unit. This causes leaks from the unit. The depth of the trap must be greater than
the negative pressure of the fan in inches of water column. A vent is sometimes installed after the
trap. If a long shallow drain line is a
problem, a condensate pump could be installed to eliminate condensate-draining
problems.
The Fan Drive and Blower
After the coils and condensate
system is the supply air fan. The fan
usually has a belt drive and an adjustable sheave on the motor side. The sheave is adjusted to control fan speed
and therefore airflow and motor current.
Airflow is adjusted to maintain the proper air and water temperature
splits.
The fan must run in the proper
direction. The type of supply air blower
used in many commercial air conditioning applications is called a forward
curved blower. The forward-cupped veins
in the blower wheel must be driven in the direction of the airflow. A fan running backwards is a reason for low
airflow.
This is the type of unit that could
easily have serviceable bearings, meaning needed lubrication.
Life/Safety Adaptations
Some areas require smoke detectors;
they may be installed in the supply and/or the return air duct. The smoke detector is usually wired in series
with the freeze-stat to shut off the fan and close the outside air. Sometimes this system becomes part of a smoke
evacuation system. Always try to know
and understand all the parts of any system you work on. In most cases, the
life/safety considerations take president over comfort when those objectives
come into conflict.
The Air Distribution System
Supply air ducts are not usually a
service issue; however two ductwork related issues are:
1. Flex duct sometimes is blown off
of the collar. It must be re-installed
with duct straps, screws and duct tape.
Flex duct is not intended for long runs.
Typically runs longer than five to ten feet are not allowed by
specifications in the blueprints.
2. Balancing dampers are used to
balance the airflow from a diffuser to meet local requirements. Balancing dampers are either at the diffuser
or at the branch duct take-off from the main trunk. The adjustment lever may be covered with
insulation at the takeoff. If they are
not in the diffuser they are probably in the takeoff.
THE HOT WATER- CHILLED WATER AIR
HANDLER
Normal problems in hot water-chilled
water air handlers include condensate leaks, dirty coils, control malfunctions,
water flow problems, and control, piping, and airflow design problems. In the
case of a steam coil, the steam trap could be a problem.
Common problems encountered when
working on these air handlers include
Controls. The modulating control system has the
temperature controls and the operating controls combined in an integrated
system. There are two basic electric
modulating control schemes, one that uses mechanical thermostats with
potentiometers and relay logic and the other is microprocessor based. They both do about the same thing. Another system is pneumatic; it uses
modulated air pressure to operate valves and dampers in response to
temperature.
Water
flow. When dealing with water flow
problems, even more than some other types of problems, it is important to
always do your maintenance first. Many
water flow problems, in equipment that did cool the site at one time, are
resolved by proper maintenance.
Airflow. Airflow problems through the hydronic air
handler are the same as the DX air handler.
The filters and coils get dirty.
The fan motor, belt, bearings, etc. can wear or break. Return air can be restricted. Additionally, return and outside air dampers
can be out of position for a variety of reasons.
TROUBLESHOOTING AIR FLOW-WATER FLOW
PROBLEMS
The central plant supplies chilled
water. The required amount of water flow
is specified on the blueprints, or can be determined with enough information
about the unit, coils, expected inlet and outlet water temperature, and the
heat load in the space. Water flow is
measured in gallons per minute. There
must be a device installed in the water line that allows water flow
measurements (i.e. Bell and Gossett Circuit Setter) if the actual flow, in
gallons per minute, is to be estimated.
This calculation requires special tools and information.
The relative amount of water flow,
airflow, and resistance to heat transfer is determined by some simple
rules. The critical measurements needed
to analyze problems with the heat transfer capacity of the chilled water system
are the entering and leaving water temperature and the entering and leaving air
temperature.
Chilled water air handler
temperature limits
Minimum
°F Maximum °F
Supply water temperature 43 48
Water ΔT 8 12
Air ΔT 15 20
Mixed air temperature 50 58
The entering water
Entering water should be between 43°F and 47°F. Entering water warmer than that indicates a
capacity problem in the central plant, consult with the central plant.
Water temperature drop or “ΔTwater”
This is the temperature of the
supply water subtracted from the temperature of the return water. It is a measure of the relative amount of
heat absorbed by the water in a Chilled Water Unit.
Generally, we want to see - 8°F to -12°F water temperature drop
across the chilled water coil.
Example: 45°F
inlet water, with 55°F
outlet water temperature means that the ΔTwater
is 10°F.
Return air
Entering air temperature should be
near to but warmer than the space temperature.
Plenum-return air may be as much as 5°F
warmer than the conditioned space temperature.
If the return air temperature is excessive, meaning more than 5°F above the space
temperature, look into economizer (excessive warm outside air) problems, or
return duct leaking in hot air.
Supply air temperature drop or “ΔTair”
This is the temperature of the
supply air subtracted from the temperature of the return air. This and dehumidification, filtration and
ventilation are the products of the machine.
Generally, we want to see a 15°F - 20°F temperature drop across
the chilled water coil
STANDARDIZED CHILLED WATER COIL
TESTS
Clean The Coil. (Check for Under-sized
Coil)
Case 1: Chilled supply water temperature is not
high -and- ΔTair
is low
-And- ΔTwater
is low
Cold supply water temperature (less
than 48°F) and a low
air temperature drop across the coil (less than 15°F) and a low water temperature drop across the
coil (less than 8°F) if
detected, indicates a dirty chilled water coil.
The coils must be cleaned. Check
for dirty filters.
Under sized coils, such as four-pass
coils will have the similar characteristics to a properly sized dirty coil.
Speed-up Supply Fan
Case 1: Chilled supply water temperature is not
high -and- ΔTwater
-and- ΔTair is high
Cold supply water temperature (less
than 48°) and a high
air temperature drop across the coil (more than 20°F) and low water temperature drop across the
coil (less than 8°) if
detected, indicate the fan is running slow.
Speed up the fan to no more than motor nameplate current (75-90% of
nameplate current is often where it should be, 50% nameplate current is usually
low). Look for return air or supply air
restrictions.
Low or Restricted Water Flow
Case 1: Chilled supply water temperature is not
high -and- Water ΔTwater is high
-and- ΔTair is low
Cold supply water temperature (less
than 48°) and a low air
temperature drop across the coil (less than 16°)
and high water temperature drop across the coil (more than 16°) if detected, indicate
water flow is less than required.
Check the chilled water valve and
hand valves to be sure they are open.
Three-way valves are open with the stem DOWN (the opposite of the more
common two-way valves). Look for a wye
strainer (on the supply line) to clean. There
usually is a “circuit setter”, a device used in balancing the system to limit
flow (on the return line). Setting the
water flow is something done to a properly running system. If after a quick analysis and it appears that
there is a water flow problem, learning the policy around the circuit setter is
the next question to ask. Either you
need to be allowed open it or someone will come with the tool to set the flow
to the units’ specification for flow.
Check the temperature drop across a
three-way valve. If the water returning
to the central plant gets colder through the valve, supply water is
bypassing. Adjust the valve stem button
to close off the by-pass, or close a by-pass line hand valve to stop all supply
water bypassing. This test is testing the control valve for internal leakage.
If the central plant is not
delivering enough chilled water, that will have to be proven, perhaps to a
skeptical audience. Resist the urge to
slow down the fan, to lower the airflow to match the restricted water
flow. Check the installed pipe size
against the blueprints.
High Supply Water Temperature
Case 1: Chilled supply water temperature is high.
If the entering water temperature is
high, go to the central plant and ask if they are having a problem maintaining
supply water temperature. Note the
reason for the problem and the estimated time for repairs. If they are not having central plant
problems, ask an engineer to look at the problems you are having with you.
COMMON PROBLEMS AND POTENTIAL
SOLUTIONS
Chilled Water Coil Piping
The entering water must enter the
coil at the air leaving side, and leaving water leaves from the air entering
side. The reasoning is that the coldest
water must interact with the coldest air, and the warmest water interacts with
the warmest air. Carrier estimates that
units with backwards water flow suffer from a 15% loss of capacity.
The piping to hot water and chilled
water air handlers are usually all right.
Aside from surveys and first visits, low water flow issues and low
capacity are usually the only reason to look into pipe size or design.
No Mixing
No mixing is when the outside air
can reach the coils and the freezestat without mixing with return air. This happens when the outside air enters the
mixing box near the coils or when outside air and return air enters at opposite
sides of a mixing box. The cold outside
air should meet the warmer return air at right angles at least 3 diameters of
the duct away from the coils.
If the central plant is not
supplying chilled water because the system is in “winter mode” and a freezestat
trip occurs, and no mixing is the cause, one tactic I have used successfully is
to drain the water from all coils and jump the freezestat. This will give dependable outside air cooling
and it will remove the possibility of freezing the coil and give good
dependable cooling until the problem is repaired. The alternative is to disable
the outside air and leave the coils filled.
This will supply heating and mechanical cooling, when available.
The air should be filtered after it
is mixed. The hot water coil comes next
in the air stream followed by the freezestat, the chilled water coil, the fan,
then and the supply duct. If any
component exists in the system outside of this order it may be a problem
Stabilizing a Job
When stabilizing a job, the usual
strategy to deal with economizer problems short term is to drain the coils and
jump the freezestat.
Some buildings rules will not allow
the coils to be drained, if this is a problem the choices are fix the problem
now, leave the unit off until the problem is fixed, or get a waiver of the mall
policy from the customer. If a
freezestat tripped and you didn’t repair the defect and you put the unit back
into service with water in the coils the best that can happen is the freezestat
will trip again and you will have a call back.
If we are unlucky and the coil does freeze and burst it can cause lots
of damage, a major repair job and maybe a lawsuit. Always be sure to leave all units without an
unreasonable risk of freezing.
(The following is something I
normally would have edited out of the public version of the story, but here is
what I would tell my employees that work in cold climates about this situation –
“Frozen coils are the most common, high consequence failure we have. We cannot do enough to avoid them. Always call your field supervisor to discuss
these types of situations before acting or leaving the job.”)
Repairs after a Frozen Coil
Repairing a hot water/chilled water
air handler after freezing has two goals.
1. Stop
the water leak
2. Solve
the problem that led to the frozen coil.
Stopping the water leak always
involves making a decision about whether or not to replace the coil. Everyone wants to repair the leak without
replacing the coil. It’s easy to make a
mistake where you spend a lot of repair time (money) and still end up having to
replace the coil anyway. You also
increase the unit’s downtime because the new coil isn’t ordered until it
becomes obvious it’s needed.
At my contracting company, we generally
try to repair leaks on return bends. We
replace coils with leaks in the body of the coil. There are times when this
overly simple rule is wrong; when it’s really wrong, repair the coil. This rule is not usually wrong.
Repairing leaks on return bends is
simply finding the leak, pushing it back into shape, clean it with sand paper,
and brazing it with 15% solder. This
will work on most leaks you can reach with your torch. If you can’t braze it for some reason, we
have used epoxy to repair water leaks.
It usually sets-up in a short time.
Sometimes it must set-up over night.
After You Repair or Replace the Coil
Whether you replace or repair the
coil, the cause of the freeze must be found and repaired. Common causes of frozen coils are no mixing,
disconnected and propped open outside air dampers, miss-set minimum position
rheostats, and especially, broken or poorly designed control systems.
(Again, internal directions to my
employees – “You may not fill a repaired or replaced coil until the control
problems are solved or the outside air damper is locked closed. Your field
supervisor must approve all aspects of a frozen coil job.”)
MAINTENANCE OF THE HOT WATER-CHILLED
WATER AIR HANDLER
Cleaning the Coil
Clean coils are essential. I have
been successful using an electric power washer and cleaning from the air entering
side of the heat coil and the air leaving side of the chilled water coil. Sometimes removing the top of the unit allows
cleaning between the coils. In some
extreme cases, because the face of the chilled water coil was plugged and there
was no other way, we have removed the unit, disassembled it on the ground, cleaned
the coils outside the unit, and put everything back together. If the fan motor is external, you may be
helped in cleaning the coil, by washing the coil with the fan running.
A good rule would be – “Never spray
water on a coil with an internal fan motor running.”
You must do what it takes to clean
the coils well enough to clear the fault, or all the effort you spend will be
for nothing.
The standard tests for chilled water
air handlers to apply when checking the effectiveness of coil cleaning effort.
Measure the key temperatures before
you start cleaning so you can gage the effect the cleaning has had. If the occupied space cools down, and the
standard tests no longer indicate a dirty coil, the coil has been effectively
cleaned. A properly running machine will
have a comfortable zone with about a 55°
supply air temperature, and an 8°-12°F ΔT on the water.
Condensate Leaks
Condensate leaks are a common
problem in this class of machine.
Leaking may be caused by one of several different problems. Dirt is a common cause of leaks. Dirt can build up in the condensate pan,
trap, or drain line. The pan and trap
must be cleaned thoroughly at coil cleanings, water leak service calls, and
whenever you see dirt or slime building up.
Dirt on the coils reduces the airflow area. This causes the air to flow through the coil
faster. The velocity can increase to the
point where condensate is being thrown off the coil by the air velocity,
filling the fan section. Cleaning the
units with a power washer will remove most causes of dirt related condensate
leaks.
Long condensate lines are common on
these air handlers. If the condensate
drain line is long and has a shallow pitch, a condensate pump may be
required. Pipe the pump’s output into
the existing drain line. Be sure to
power the pump from a circuit that remains on 24 hours a day.
Chilled water lines, including the
strainer and all valves should be insulated.
The condensate that forms on these parts may be the cause of chronic
nuisance water leak problems.
Motors, Belts and Bearings
Maintenance of the motors, belts and
bearings is the same here as in other air handlers. Check belts and replace them as needed. Overly tight belts will destroy
bearings. Listen for bearing noise,
check for bearing play if you hear or feel something that makes you suspicious
of the bearings. Grease and oil
non-sealed bearings as needed. Grease bearings sparingly; no more than once per
year at the cooling start-up maintenance inspection. Generally, installing grease fittings on
bearings that don’t already have them is not encouraged.
Check the alignment of sheaves and
repair as needed. The surfaces of the sheaves
where the belt rides are shaped like a “V”.
If the faces are shaped more like a “U” the sheave must be replaced as
warn. Install the guard over the belts
whenever they are off, before you leave the job.
CONCLUSION
The hot water/ chilled water air
handler is very similar to, yet very different from the DX air handler. The controls are less well understood by the
average mechanic. The heat transfer
rules are easy. If the entering water is
cold, and the leaving water is too warm, you need more water flow. If the leaving water is cold, either speed up
the fan or clean the coils.
The main risk of operating this kind
of equipment is the potential for huge amounts of water coming through the
ceiling in the middle of the night because a frozen and busted water-filled
coil. If there is a danger of that
happening, lock off the economizer or drain the coils. You may need heat. If so, the only choice seems to be to lock
off the economizer so that the heat coil may be filled.
The central plant is responsible to
deliver the proper amount of chilled water. If they can’t or won’t the best
course of action for a tech is to make documentation. Get the evidence that will be needed when this
problem reaches a point where it must be solved. Be sure to document a clean and well
maintained unit, the names of the people met with, the times and dates of the
meetings and what was said.
Your writings, articles, blogs I mean over all contents is must read matter. air conditioner repair
ReplyDeleteOutstanding blog post, I have marked your site so ideally I’ll see much more on this subject in the foreseeable future. steel castings
ReplyDeleteThis is the type of information I’ve long been trying to find. Thank you for writing this information. hot water repairs melbourne
ReplyDeleteLove to read it,Waiting For More new Update and I Already Read your Recent Post its Great Thanks. OMC engine water pump
ReplyDeleteI just could not depart your website before suggesting that I really loved the usual info an individual provide for your guests? Is going to be again often to investigate cross-check new posts. home water filtration system
ReplyDeletePretty good post. I just stumbled upon your blog and wanted to say that I have really enjoyed reading your blog posts. Any way I'll be subscribing to your feed and I hope you post again soon. Big thanks for the useful info Single-use Diaphragm Valves
ReplyDeleteThis is such a great resource that you are providing and you give it away for free. I love seeing blog that understand the value of providing a quality resource for free. Boiler repairs
ReplyDeleteYour blogs are easily accessible and quite enlightening so keep doing the amazing work guys. go now
ReplyDeleteWhoi, excellent, t wondered just how to cure icne. ind found your webstte by google, dtscovered todiy t'm i ltttle obvtous i greit deil. t’ve ilso idded RSS ind sive your webstte. keep us updited. water softener hardness chart
ReplyDeleteThanks for the blog post buddy! Keep them coming... water discharge hoses
ReplyDeleteHello I am so delighted I located your blog, I really located you by mistake, while I was watching on google for something else, Anyways I am here now and could just like to say thank for a tremendous post and a all round entertaining website. Please do keep up the great work. telecomando aria condizionata
ReplyDeleteExcellent article. Very interesting to read. I really love to read such a nice article. Thanks! keep rocking. water valve supplier
ReplyDeleteAwesome review, I am a major devotee to remarking on web journals to educate the web journal scholars realize that they've added something beneficial to the internet!.. portable air conditioners
ReplyDeleteThank you because you have been willing to share information with us. we will always appreciate all you have done here because I know you are very concerned with our. Warmtepompen
ReplyDeleteA debt of gratitude is in order for the significant data and experiences you have so given here... Rain Go
ReplyDeleteGreat post! I am actually getting ready to across this information, is very helpful my friend. Also great blog here with all of the valuable information you have. Keep up the good work you are doing here. Gutter installation Contractor Raleigh NC
ReplyDeleteI am a new user of this site so here i saw multiple articles and posts posted by this site,I curious more interest in some of them hope you will give more information on this topics in your next articles. Zonnepanelen
ReplyDeleteI am hoping the same best effort from you in the future as well. In fact your creative writing skills has inspired me. Airco
ReplyDeleteThis was incredibly an exquisite implementation of your ideas Airco
ReplyDeleteI’m excited to uncover this page. I need to to thank you for ones time for this particularly fantastic read!! I definitely really liked every part of it and i also have you saved to fav to look at new information in your site. Airco
ReplyDeleteYour blog provided us with valuable information to work with. Each & every tips of your post are awesome. Thanks a lot for sharing. Keep blogging, Gutters Raleigh
ReplyDeleteI found so many interesting stuff in your blog especially its discussion. From the tons of comments on your articles, I guess I am not the only one having all the enjoyment here! keep up the good work... visit website
ReplyDeleteMuch obliged to you for peopling get the data they require. Extraordinary stuff of course. Keep up the colossal work!!! Gutter installation companies
ReplyDeleteThis is an important capacity issue, the coldest water should interact with the coldest air.commercial
ReplyDeleteWow! Such an amazing and helpful post this is. I really really love it. It's so good and so awesome. I am just amazed. I hope that you continue to do your work like this in the future also Airconditioning
ReplyDeleteReally enjoyed this blog article.Thanks Again. Really Great. tks industrial company
ReplyDeletePretty good post. I just stumbled upon your blog and wanted to say that I have really enjoyed reading your blog posts. Any way I'll be subscribing to your feed and I hope you post again soon. Big thanks for the useful info Shallow drain
ReplyDeleteoutsourcingall.com "Usually I never comment on blogs but your article is so convincing that I never stop myself to say something about it.
ReplyDeleteThis paragraph gives clear idea for the new viewers of blogging, Thanks you. You’re doing a great job Man, Keep it up.
outsourcing training
I admire this article for the well-researched content and excellent wording. I got so involved in this material that I couldn’t stop reading. I am impressed with your work and skill. Thank you so much. https://aquafiltermag.com
ReplyDeleteThis is such a great resource that you are providing and you give it away for free. I love seeing blog that understand the value of providing a quality resource for free. Water heater repair Jurupa Valley
ReplyDeleteThis is a great inspiring article.I am pretty much pleased with your good work.You put really very helpful information. Keep it up. Keep blogging. Looking to reading your next post. oil tank removal
ReplyDeleteRegular visits listed here are the easiest method to appreciate your energy, which is why why I am going to the website everyday, searching for new, interesting info. Many, thank you air quality testing
ReplyDeleteYou there, this is really good post here. Thanks for taking the time to post such valuable information. Quality content is what always gets the visitors coming. aircon servicing singapore
ReplyDeleteHello, this weekend is good for me, since this time i am reading this enormous informative article here at my home. エアコンクリーニング 大阪
ReplyDeleteI see the superlative contents on your blogs. we provide air duct cleaning arlington heights at affordable prices. for more info visit our website.
ReplyDeleteThanks for sharing an informative content.
ReplyDeleteAircon servicing
its one the good blog for aircon installation i loved it.
ReplyDelete#aircon installation
https://airconpros.com.sg/aircon-installation/
You did great job..Thank you...Aircon about info visit mine..
ReplyDeletehttps://surecool.com.sg/
#aircon service
Simply superb, i get lot of useful info thank you...
ReplyDelete#Coolcare
https://coolcare.com.sg/
https://coolcare.com.sg/
I have seen some posts on this website and I think that your blog is very interesting and has lots of excellent information. we provide duct cleaning bartlett at cheap cost. for more info visit our website.
ReplyDeletethis is the very intresting blog
ReplyDeleteThis is helpful hope you can make more articles like this. BTW guys if you need a Airconditioning Service Company you can call or visit [Yeobuild HomeCool](https://homecool.com.sg/)
ReplyDeleteI really like your writing style, great information, thankyou for posting. Air Comfort Technologies
ReplyDelete